2.18 - 240404

4. April 2024

Normal Update

After upgrading to this firmware version, it is no longer possible to downgrade to a lower version.

Added Features

  • Added SNMP Traps Filter [T4987]
  • BACS: Add CS Sensor Events [T772]
  • Configurable SensorLog Rate [T5062]
  • Add a Secondary Remote Syslog Server [T5113]
  • BACS: Provide new Alarm2 Flags via Modbus [T4689]
  • BACS: Support new product type BACSKIT_BM4 [T4245]
  • BACS: Calibrate Current Sensor through the Webmanager [T5060]
  • BACS Battery Charge [%] Threshold & Event Introduction [T4819]
  • BACS: Support CSHxxx AC Current Values in BACSViewer [T3619]
  • Failed login attempts should be logged [T5047]
  • CSH-Sensor: Add "Ground Fault" detection [T4760]
  • Add Fw version and serial number to the BACnet values [T5165]

Changed Functionality

  • Add new favicons for various OEMs [T5202]
  • Prevent downgrade to older firmware [T5149]
  • BACS: Adjust low voltage alarm threshold cap to 13.25 [T5182]
  • Label for the activation of e-mail traps supplemented by UNMS [T5059]
  • BACS: Removed bacsLogRate's and bacsImpcPollRate from MIB file [T5153]
  • Toggle UPS Outlets should show a message box to confirm on off [T5055]
  • BACS: Apply delay of "Discharge Volt Alarm" to "Max. Voltage Difference" as well [T3530]

Bug Fixes

  • Password hashes are not salted [T5002]
  • SerialTrace may not work after a reboot [T5159]
  • SSH UI indicates ON when off by default [T5127]
  • SSH server version is outdated and vulnerable [T5003]
  • Insecure protocols may be migrated across updates [T5123]
  • Restrict SFTP access of the admin user to log files [T5135]
  • Users should be warned when enabling insecure Protocols [T5122]
  • RCCMD TLS/SSL trap jobs execution may fail with 'system error' [T5204]
  • 'Serial Trace' accepts insecure connections using TLS 1.0 and 1.1 [T5121]
  • BACS: If Ri is outside the threshold no alarm will be triggered [T774]
  • Sensormanager/SM_T_COM Modbus registers error when UPS is disabled [T5043]
  • BACS: Equalizing should not switch off at RI-Alarm [T4669]
  • BACS: "Fuse blown" don't trigger "BACS General Alarm" [T5156]
  • SNMP service: Switching from protocol v3 to v2 sometimes fails [T5194]
  • The configuration of SMS jobs can trigger errors during sending [T5068]
  • $$PRABLER3 (Continuity Plus 6000): The Error id field in the monitor screen sticks out of the screen [T5155]
  • UPS Monitor Problem with new Chrome/Edge Version [T5247]

OEM customer specific features, changes and fixes

  • OEM 002: Added the UPS "Protect C (LCD+) 1-3kVA" and "Protect D (LCD+) 1-3kVA"
  • OEM 007: Added the STS "Master Switch STS 3P/4P"
  • OEM 008: Implementation of Keor MOD Ri [T5186]
  • OEM 008: Require password change after the 1st login [T5069]
  • OEM 008: $$TRIMOD: Scheduler job handling is not working properly [T5198]
  • OEM 011: Added the UPS "Ablerex Thor series"
  • OEM 012: Added the UPS "Ablerex Thor series", "G-Tec Matrix", "Voltronic Winner Pro", "AEC IST7", "DELPHYS GP 2.0 Touch 160-800kVA" and STS "Master Switch STS 3P/4P"
  • OEM 012: Socomec Netys NRT 2 1100VA sends invalid status messages [T5061]
  • OEM 017: Missing Modbus value at MD-1000PRO Slot [T4952]
  • OEM 020: Added the UPS "6.0 kVA Tactical UPS"
  • OEM 021: Added the STS "Master Switch STS 3P/4P"
  • OEM 028: $$PRABLER3 (Continuity Plus 6000): Missing Reset output energy consumption button [T5154]
  • OEM 030: Add RIELLO UPS modellrange [T5040]
  • OEM 032: Implementation New Kstar 3/1 UPS's [T4975]
  • OEM 034 Allow config transfer for Fw updates between OEM 34 and 68 [T5075]
  • OEM 034: SNMP V3 User name does not display if space is present [T5083]
  • OEM 035: $$EVO2 - "JOVYSTAR-PLUS-E": Various Improvements [T5051]
  • OEM 035: $$JOVY - "JOVYSTAR-delta RS232": Various Improvements [T5050]
  • OEM 035: Wrong UPS Status at SSB (static Bypass) Operation [T5046]
  • OEM 035: Jovytech PE/PME DC 72V: Missing OID=33.1.4.4.1.4.1 and Screen info [T5072]
  • OEM 036: $$CONCE: RCCMD TLS/SSL trap jobs may block other jobs [T5197]
  • OEM 036: $$CONCE "DPA": Constant reboots if 10 or more modules are connected [T5190]
  • OEM 044: Added the UPS "Modular UPS MD"
  • OEM 045: Remote Command extension ATS command [T5037]
  • OEM 045: Added the "WP-S (S2)" UPS"
  • OEM 048: Added the STS "Master Switch STS 3P/4P"
  • OEM 057: Added the UPS "PowerWAVE ELMOD Series"
  • OEM 057: $$BPC_ELMOD (PowerTower Green): c=Create an own Modbus section [T5042]
  • OEM 064: Added the STS "Master Switch STS 3P/4P"
  • OEM 068: Changed to Schneider with Gutor UPS model list
  • OEM 068: Change BACnet Vendor information based on OEM [T5163]
  • OEM 070: UPS type 11: Some Modbus values starting from address 280 are wrong [T5110]
  • OEM 077: Added the STS "Master Switch STS 3P/4P"
  • OEM 078: Added the UPS "EAST-LION 3000" and STS "Master Switch STS 3P/4P"
  • OEM 082: Implementation "CS-IS" DC/AC Converter [T5081]
  • OEM 082: $$MBCUBE4 (SLC CUBE 4 >=30kVA) SNMP values for upsOutputPower are missing [T5107]
  • OEM 084: $$PREXTCRC: UPS Events History Headline/Fault Text [T5071]
  • OEM 084: Added the UPS "PowerTower Green", "PowerPro ELMOD" and "PowerWAVE EL300DSP Series"
  • OEM 085: Added the UPS "Ablerex THOR series" and STS "Master Switch STS 3P/4P"
  • OEM 087: $$PRABLER3: Outlet Switching [T5076]
  • OEM 087: Added the UPS "Mini J RT PRO III" 1-3kVA and "Midi J (A)" 10-20kVA"
  • OEM 092: Added the UPS "XTCEN"

2.16 - 230714

14. July 2023

Normal Update

Added Features

  • Reimplement and improve firmware update check [T4300]
  • BACS: Introduction of a new impedance error ""Blown RI Fuse" [T4028]
  • BACS: Display of Average Resistance Value [T4765]
  • MIB Extension for UPS's with pos. & neg. Battvolt/Battcurrent [T4982]

Changed Functionality

  • SM_T_COM/SM_T_H_COM Visualization improvement [T4979]
  • Some SNMP traps contain more objects than defined in the MIB [T5008]
  • BACS: Setup Screen: Allow only integers when entering "Nominal Capacity per Battery [T4668]
  • BACS: Apply delay of "Discharge Volt Alarm" to "Max. Voltage Difference" as well [T3530]

Bug Fixes

  • RCE vulnerability in NTP configuration [T4989]
  • SNMP service is partially active after factory reset [T4995]
  • UPS RS232 communication does not start when a load higher than the power has been configured [T5006]
  • SiteManager 6: Archived log files are listed with date 1970 [T4970]
  • Wrong warning about "Gateway is in other subnet" may appear [T4911]
  • Integration of RS485 Modbus fix for CS141LM HW 161 [T4998]
  • BACS: SNMP resistance query is not answered before first measurement [T3859]
  • BACS: Indicate that the RI measuring value is outside the module measuring range [T3695]
  • BACS: No audible browser confirmation at last programmed module [T4766]

OEM customer specific features, changes and fixes

  • OEM 004: $$PREXTXANTO, $$PREXTZINTO, difference between UPS screen values and SNMP values [T4967]
  • OEM 004: $$PREXTZINTO (ZINTO 1000 (Mod.2017)): Charger failure will not be recognized [T4997]
  • OEM 008: KEOR MOD, $$KEORMOD, SNMP upsOutputPower values are wrong [T4964]
  • OEM 008: $$KEORMOD (KEOR MOD): Add event "External Battery Switch open" [T4965]
  • OEM 008: Added "KEOR XPE" modular UPS
  • OEM 012: Added "KEHUA MR33" modular UPS series
  • OEM 015: Renamed PowerValue G2 series
  • OEM 017: Missing Modbus value at MD-1000PRO Slot [T4952]
  • OEM 017: New Protocol for ML RT 750 GEN ID 436 [T4980]
  • OEM 022: $$MBTAURUS: System Screen Temperature Values "0.00°C" [T4895]
  • OEM 025: Changed "Rubin Plus 6-10 kW" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 028: $$GPSER (X-Plus MST 40): Scheduler battery test is no longer working [T4974]
  • OEM 028: Changed "Continuity Plus 6kvA/10kVa" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 029: Renamed PowerValue G2 series
  • OEM 035: Added "JOVYSKY Q" UPS
  • OEM 036: $$XONL12C: (Power Value 1/1 (R)(T)1-10kVA): Scheduler battery test is no longer working [T4983]
  • OEM 036: Renamed PowerValue G2 series
  • OEM 045: Renamed UPS series "Convert II" to "CON2"
  • OEM 045: Added "KEHUA MR33" modular UPS series
  • OEM 047: Changed "DK Plus 6kVA/10kVA" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 050: $$CENTIEL2: Scheduled battery test fails with invalid argument [T4450]
  • OEM 050: $$PRABLER(3): Wrong UPS Autonomy Time [T4408]
  • OEM 057: Added "PowerTower Green" modular UPS
  • OEM 059: Changed "Continuity Plus 6kvA/10kVa" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 061: Added "Matrix 1-3kVA" and "HUAWEI E/G/A" UPS series
  • OEM 062: Changed "Minicompact 2 6kW/10kw" protocol from "$$PRABLER2" to "PRABLER3" with Q4, Q5, At and BL command
  • OEM 066: Added "Ultron DPS Gen.2" series, "Ultron HPH Gen.2" series and "Modulon DPH" series
  • OEM 078: Integration of Matrix MXT/MXRT UPS series [T4988]
  • OEM 084: Updated their OEM Logo
  • OEM 087: Added UPS "Midi 10-100 series", "Midi J S series", "Maxi 10 - 800 series" and "Maxi J S series"

2.14 - 230329

29. March 2023

Normal Update

Added Features

  • BACS: Add Discharge Counter Reset option [T3470]
  • Implement encryption for the UPSTCP protocol [T4863]
  • Show warning message when default password is used [T4887]
  • Enable configuration of multiple email trap recipients [T4880]
  • Display the #LOCATION variable in a more prominent position [T4853]

Changed Functionality

  • Turn on TLS for RCCMD & UNMS services by default [T4955]
  • Display the contents of the Datalog as a table view [T4303]
  • Megatec 3-phase series:, $$MEGA, $$MEGAE CS141 UPS screens improvement [T4875]
  • BACS: After discharging, keep the higher log rate for a short time [T2866]

Bug Fixes

  • Wrong Analog Sensor Events at SITEMANAGER 6 [T4630]
  • "Forgot password" reset procedure no longer works [T4933]
  • With series SCM on hw161 the RS485 interface does not work [T4969]
  • Unsupported Modbus addresses that have a factor defined will be displayed [T4922]
  • Local admin can not log in if option "Radius, than local" is enabled without RADIUS server [T4862]
  • $$MEGA(E) (Megatec 3-phase): Display of Ext. information values overlap the input icon [T4875]
  • New Netfinder available for searching CS141 with SSL/TLS encryption in networks - available from GENEREX website as free download
  • ALL OEMs using APC SNMP network cards Type 2 and MGE Galaxy 300 with UNMS : New UNMS fixed communication issues [T4949]

OEM customer specific features, changes and fixes

  • OEM 003: Apotrans III: Replace "UPS" with "STS" in the "UPS Event History" menu item [T4873]
  • OEM 004: $$PREXTXANTO: ComLost/Restored several times per day [T4884]
  • OEM 004: UPS function "Battery deep discharge protection" does not work [T4957]
  • OEM 008: $$KEORMOD (KEOR MOD): Add event "External Battery Switch open" [T4965]
  • OEM 011: New OEM Partner SANDERElektrische Anlagen - first version - supporting all standard UPS from OEM ID 12
  • OEM 022: BORRI Legrand changed SNMP traps for EVO series of battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 035: $$EVO2 (JOVYSTAR-PLUS-E): Various measured values require corrections [T4846]
  • OEM 035: JOVYATLAS typo in UPS modellist JOVYTEC L series corrected
  • OEM 038: ASTRID changed SNMP traps for EVO series of battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 039: KAMIC Sweden has changed their Logo
  • OEM 045: MGESHUT3 (Windstar UPS): UPS custom thresholds no longer at present [T4973]
  • OEM 047: S2S Legrand changed the protocol for KEOR HPE to "EVO5"
  • OEM 050: Add SNMP variable for Output Energy Consumption [T4897]
  • OEM 050: $$CENTIEL2 (Centiel UPS (since 2020)): Add Input Current Values [T4919]
  • OEM 050: $$CENTIEL/$$CENTIEL2 Removed UPS Control Function [T4920]
  • OEM 055: Integration of "Kehua MYSerie" UPS protocol [T4929]
  • OEM 055: COROMOATC added "DELPHYS GP 2.0 Touch 160-800kVA"
  • OEM 056: PTI Predictive Technology USA received new FAVICON
  • OEM 065: ELINEX has changed their Logo
  • OEM 070: ASTRID NEUTRAL changed SNMP traps for EVO series "Device Type 1" battery bad A1,A6,A9,A10,A16,A20,A23,A24,A51 from red (Alarm) to blue (Informational)
  • OEM 071: Implementation Voltronic Arena UPS [T4915]
  • OEM 071: INFOSEC France added "Mod3" with Voltzronic protocol PREXTMULTI
  • OEM 077: $$XONL12 (Power Value 1/1 (R)(T) 1-10kVA): Show temperature on UPS screen [T4947]
  • OEM 077: $$XONL12C (Power Value 1/1 (R)(T) 1-10kVA): Wrong statuses are displayed during the battery test [T4958]
  • OEM 082: $$MBADAPT2 (SLC ADAPT2): Use ADAPT-X modbus mapping [T4805]
  • OEM 087: $$MBSALIRM2 "HiUp series" Event & Screen Extension [T4903]
  • OEM 087: $$MDELTA: Wrong calculation of autonomy time when UPS does not support it [T4948]