1.58 - 170627

27. June 2017

Normal Update

Added Features

  • Added function to delete BACS Logfiles [T2940/T38 and #3368]
  • Added function to delete EventLog and DataLog [T92/#3286]
  • Added function for BACS Viewer to display Firmwareversion [#687]
  • Added delay of BACS Voltage Alarm after a discharge [T2863]
  • Added input of multiple IP-adresses in RCCMD Job configuration [T101/#3271]
  • Added SNMP OID for total number of modules in alarm or warning on the BACS System system Goldman Sachs [T2903]
  • Added: Support of UNMS Emailtraps for the BACS-Screen [T203/#3147]
  • Added: At AUX Job 'SensorMan Outlet' now added Logentries for Output Off [T7/#3405]
  • Added: BACS Email trap support added [T203/#3147]
  • Added: Scheduler implemented [T719/#2351]
  • Added: Function to delete BACS Logfiles [T2940]
  • Added: configurable delay of BACS Voltage Alarms after a discharge [T2863]
  • Added: SNMP OID for total number of modules in alarm or warning on the BACS System [T2903 Goldman Sachs]
  • Added: BACS support for 512 Modules and 16 Strings [T2968 + T210/#3149]

Changed Functionality

  • Changed: Protocol TOSHIBASEC (Toshiba SEC 9600b) - Add a third option for UPS efficiency value [T2927]
  • Changed: Protocol XONL12, AETSER and all other Centralion protocols, now using BT? [T31/#3376]
  • Changed: Moved 'About' menu item under 'System' and adjusted layout
  • Changed: Removed compatibility Link 'Services/Timeserver'
  • Changed: Mitsubishi 2033A,9700 protocol MITSU had startup issues, timeouts increased [T2944]
  • Changed: BACS viewer automatic report title changed #3013
  • Changed: Multiple IP-Adresses in RCCMD Jobs [T101/#3271]
  • Changed: moved 'About' menue under 'System' and adjusted layout

Bug Fixes

  • Bugfix: BACS Logfiles rotating did not work, fixed with this version [T2943]
  • Bugfix: BACS did not increase Lograte at discharge at FW 1.56, fixed with this version [T2956]
  • Bugfix: TOSHIBASEC Overload Alarm not showing up [T2860] and [T2933]
  • Bugfix: CS141 does not notify usage of HTTPS to UNMS [T37/#3369]
  • Bugfix: SNMP upsAlarmDescriptionID up-count fixed with this version [T2922]
  • Bugfix: UPS Alert history transmission through email fixed [T11/#3400]
  • Bugfix: SENSORMANAGER Events Analog Input, Digital Inputs alarm off did not work, corrected with this version [T2938]
  • Bugfix: Translations corrected [T157/#3199]
  • Bugfix: Event configuration now configurable up to 4 hours
  • Bugfix: UPS Alert history is now attached to emails [T11]
  • Bugfix: SNMP values for AUX States are wrong [T2962]
  • Bugfix: Duplicated RCCMD job receivers: regression since [1.56] [T101/T2969]
  • Bugfix: At AUX Job 'SensorMan Outlet' now added logentries for "Output-Off" [T7/#3405]
  • Bugfix: Events with GETRESULT(#-n) or GETLASTRESULT(#-n) for n!=1 fixed with this version [T2938]

OEM customer specific features, changes and fixes

  • ONLINE: Minor changes on new "ZINTO 800 - 3000 VA (Mod.2017)" [T2929]
  • Implementation of new "XANTO 6000 - 20000 VA (Mod.2017)" [T2853]
  • Bugfix XONL12A - false alarm at SNMP Variable upsAlarmWarningStatus [#3316]
  • OEM 070: Minor changes on new UPS-Protokoll UPS Type 12 einbinden [T2908]
  • WOEHRLE: Ablerex TAURUS MODBUS protocol MBTAURUS, Disable UPS OFF signal [T359/#2958]
  • AEG: Protect 3. M GRIPOW Output Current now corrected in UPS Screen [T2886]
  • Protect Plus M600 INVT/MBSALIRM Colors changed at 'On Battery' [T2921]
  • Protect Plus M600 INVT/MBSALIRM correcte AutonomyTime Display after Batterytest [T2920]
  • PILLER : APOTRANS II values unsigned u. switching voltage problem fixed [T296/#3035]
  • AP Premium Adapter-Events [#3403] T9 & T296
  • Bugfix APOTRANS_III Events logic [T2874]
  • LEGRAND: Megaline ECONT2 Device Functions corrected [T2925]
  • TRIMOD Power Modules, Misc Data, Inverter/Booster Temperatures corrected [T2945]
  • DK Plus series added with 9600 baud as default [T1830]
  • TRIMOD load display over 100% causes wrong autonomytime, corrected [T2942]
  • Bugfix for TRIMOD in UNMS, now working with UPSTCP and with SNMP RFC 1628 [T2954]
  • ABB: CONCE Alarm Input Bad (XID 618) added to MODBUS Address 120 [T76/#3309]
  • SNMP upsAlarmDescriptionID counter corrected [T2922]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]
  • ALTERVAC: AETSER via UPS Functions initiated shutdown/restore now fixed [T2906]
  • AGIT: KSTAR (Agpower ETX 10-500kVA Modbus) wrong status displayed without batteries, corrected [T2894]
  • $$XONL12C: Custom Screen for Agpower C RT 1-10kVA' [T36/#3370]
  • $$XONL12B: Custom Screen for 'Agpower D T 10-20kVA' [T218/#3125]
  • COROMATIC: Added new UPS models "JBUS Modulys", "JBUS Delphys MX/MP", "JBUS Delphys BC", "JBUS Statys" [T481/- #2779]
  • SALICRU: Added Transferswitches "SPS 16 ATS", "SPS 32 ATS" with protocol STSABLER
  • Added modular values on INVT/ADAPT-X UPS
  • Added SLC-TWIN PRO2 and RT2 series
  • KESS: batterX Hybrid USV Implementierung [T256/#3086]
  • SNG: New OEM SNG Australia as OEM ID 77, first OEM version 77 release
  • MULTIMATIC: Added "MD-XSerie 60-125kVA"
  • PowerControl UK: New OEM Powercontrol OEM ID 74, first OEM version 74 release
  • KESS: Battery X T256/#3086 fixed
  • EATON: MGESHUT at EATON UPS ID319 cause error at UPS functions, fixed
  • EFFEKTA: Added CENTRALION Transferswitch as EFFEKTA ATS 16 [T2955]
  • INVT: Added modular values
  • CET: CE+T private MIB f. Model Agil implemented [T441/#2838]
  • ASTRID: Added new UPS-Protocol as UPS Type 12 [T2908]
  • CENTIEL: UPS Events (History) Handling [ID: 10] [T152/#3204]

1.56 - 170512

12. May 2017

Normal Update

Added Features

  • New default at BACS: #3379 - to improve the scanrates at a discharge, a new configuration option is availalbe "Optimized Scan". (Default ON).
    • This function does improve the voltage updates during a discharge.
  • T79 (#3306): Introduced workaround for false Red LED on BACS modules: Those BACS modules show a red LED although no alarm is present.
    • It is caused be external noise issues and affected is only ID 1 and ID 257. Workaround: During RI measuring the thresholds of ID 1 and ID 257 are checked if there is any threshold lower than 0.01, if this is the case, BACS WEBMANAGER is resetting the threshold to 0.01 and resets the alarmbit, which turns the LED green again.
  • T2907: At BACS C40 modules measuring batteries with less than 0.02 mOhm will now appear a new information on the BACS screen that the actual values are < 0.02mOhm (before: N/A)
  • T2862: Free configurable BACS temperature thresholds added
  • T506: CS141 BUZZER as AUX-Device implemented [#2747]
  • T157: Translations added [#3199]

Changed Functionality

  • T57: DataLog Chart timeline improvement [#3342]
  • T2875: About-Page added more informations

Bug Fixes

  • T2913: Fix for BUZZER Event Configuration Server Error (400)
  • 3400: UPS Alert history through Email fixed

  • T2859: Before changing a ups model, the CS141 does now allow to save the previous configuration
  • T2877: Change form C° to F° will now also adjust the Thresholds
  • T1974: RCCMD is missing the up/downn button, Rccmd redundancy configuration and test button was missing
  • T2910: Fix for SENSORMANAGER, apply button activated
  • Com 1 noise issue: T308 - If a UPs trasnmitts noise over the RS232 cable to the COM1 of the CS141,
    it could happen that the device does not start. (No webserver). If the noise level is not removed (by
    isolating the RS232 cable), than the enduser would not see that the noise is the cause of the issue
    and the problem is related to the CS141 - which is wrong. In this firmware we introduce a noise filter
    on COM1, in case noise causes a crippled RS232 communication, the CS141 does now now start up and the
    webinterface will be available, but it still does not guarantee that the CS141 can communicate with the
    noise emitting UPS. But this firmware changes makes it obvious for the enduser that the UPS is the cause
    of the problem, not the CS141

OEM customer specific features, changes and fixes

  • COROMATIC: Changed baudrate of "ITYS2 1000-100000VA UPS 230V" from 9600 to 2400 baud
  • SALICRU: T81: $$MBSALIRM, added internal Modbus values [#3304]
  • WOEHRLE: added CONVERT 1000-3000S2 and WISUS WP (CENTIEL)
  • SAPOTEC: removed "Sapotec Serie ZP-20K"
  • EFFEKTA: change at ADIRA (XONL12C)
  • ONLINE: added ZINOT 2017 and XANTO 2017 series with new PREXT protocol
  • LEGRAND: T2880 ($$ECONT2) Megaline Screen values corrected
  • PILLER: T9: AP Premium Adapter-Events [#3403]
  • CENTIEL: T2881 added Modbus section, T16 $$Centiel: Ups Alarm History Text updated [#3393]
  • POWERNET Finnland: T61 - further changes on Powernet DAC screen (#3388)
  • CET: T2890 - CET TSI Screen changes
  • all customers using TOSHIBA protocol SEC 9600: T2891 - Fix for upsInputTruePower at SNMP

1.54 - 170405

5. April 2017

Normal Update

Added Features

  • Timeserver tests are now returning a result in the CS141 logfile
  • First version supporting CS141 BUZZER as AUX device T506/#2747

Changed Functionality

  • Text adjustments in german language mode T157/#3199 and french T41/#3363

Bug Fixes

  • "Optimized Scan" button fixed T29/#3379
  • Shutdown RCCMD signal changed for AS400/iSeries compliance, fixed with this version #3385
  • Fahrenheit / Celsius configuration fixed on all UPs screens T405/#2890
  • Webserver frontend timeout increased to avoid error messages "<503> backend busy”
  • Bugfix on BACS Programmer Webpage in CS141/B4 T2865

OEM customer specific features, changes and fixes

  • AEG: Modelname Protect Plus M600 changed, interal Modbus registers now transferred to Modbus over IP #3304
  • ADPOS: Energycounter added to Sensormanager T114/#3253
  • ABB all : Emailtrap configuration changed to notify the user about missing input T13/#3397,
    $$CONCE, Timeserver - UPS Time Synchronisation did not work correct, fixed with this version T1/#3412
  • ABB ID36: SSB project - #3407 - Protocol CONCE, backend hangup fixed when only 1 input line found (upsdev v1078,
    Emailtrap configuration changed to notify the user about missing input T13/#3397
    $$CONCE, Timeserver - UPS Time Synchronisation did not work correct, fixed with this version T1/#3412
    $$CONCE: System measures of disappeared module still visible T18/#3391
  • BORRI/ASTRID: Change log entry at $$EVO2 + $$EVO3 - if ups communication was lost, the log entry if the job "Event System Shutdown2 is logged T1082/#1895
  • EFFEKTA: Changed protocol of EFFEKTA Adira 1/1 6kVA" to $$XONL12C (before CONQ) and EFFEKTA Adira 1/1 10kVA" = $$XONL12C
  • KESS: Changes on BatteryX implementation T256/#3086
  • ONLINE: First firmware supporting new ZINTO 2017 and XANTO 2017 T67/#3022
  • LEGRAND: First version of integration Ablerex DK Plus UPS with JBUSMODULYS protocol #3290 (not finished)
    TRIMOD, TRIMODHE: Fix at SNMP value upsEstimatedMinutes remaining T2861
  • PILLER: Attach UPS alarmlog to Emailjobs added T269/#3066, APOTRANS III Display corrected T46/#3357,
    AP Premium Adapter-Events added T9/#3403
  • CENTIEL: UPS Events (History) display [ID: 11] [T151/#3205] changed, sN display corrected [T153/#3203] and T151/#3205
  • S2S: Added all LEGRAND UPS models
  • DFM Select and all customers using UPS standard screens: Screen change - added 2nd input line #3402
  • all customers using SALISEC protocols (ID 1 and 12): Modbus values extended
  • GRUENCO: Batteryvoltage value for MARS RT 2000 adjusted
  • CONTROLLED POWER: Load display changed at "UltraLITE (240 or 208V in-out)"$$CPUSA T2850