1.82 - 190820

20. August 2019

Important Update

After upgrading to this firmware version, it is no longer possible to downgrade to a lower version.

Added Features

  • Major firmware system update for increased security and reliability [T3108]
  • Email-Traps support added for SiteMonitor
  • BACS: SNMP Values for bacsAvModuleVolt and bacsTotalVolt [T3906]
  • RCCMD client passwort restrictions improved (5 characters minimum)

Changed Functionality

  • BACS improved 'Discharge detection source = Automatic' [T3784]
  • BACS accelerate measurement interval for impedance (RI) [T3896]
  • BACS current sensors CSH400/2000 measurement accuracy increased [T2993]
  • UNMMS protocol "RFC 1628 SNMP" alarm detection now less strict implemented to avoid issues with 3rd party SNMP cards not sending the correct number of SNMP alarms at upsAlarmsPresent.0 (HUWAEI and EATON cards)

Bug Fixes

  • BACS: C40 modules will longer not generate 'impedance high' alarm if value is out of range [T3734, T2907]
  • Configuration issues for SITEMANAGER and SITEMONITOR at COM2 fixed [T3879]
  • SITEMANAGER 6 added SM_II_DIG sensor [T3876]
  • Custom Threshold "UPS Temperature High Alarm off" job fixed [T3799]
  • Email Bulk edit beyond 60 jobs per event caused "Server Error (413). Error message now "Too many jobs" [T3883]
  • UNMS added E-Mail Traps for SENSORMANAGER and added UPS/CS141 link button and the names for digital IO's
  • Fixed internal reset to UTC timezone during update [T3911]
  • SITEMANAGER/SITEMONITOR 6 configuration COM 2/3 [T3918]

OEM customer specific features, changes and fixes

  • OEM 002: AEG new Protect C (LCD) implemented [T3658]
  • OEM 002: AEG first version of "CS141BSC/L as "LC" (Low Cost" series with limited UPS support up to 6KVA
  • OEM 003: PILLER Function Screen Changes [T3887]
  • OEM 003: GXSERVE Daemon memory leak problem solved by OutOfMemory-Guard service [T3605]
  • OEM 003: At "AP PREMIUM" the name "UPS" changed to "Converter" [T3909]
  • OEM 004: ONLINE Xanto 2017, $$PREXTXANTO, Changes on UPS Functions [T3924]
  • OEM 008: LEGRAND implementation KEOR PDU 800 [T3881] and UPS model list sorted aphabetically
  • OEM 008: LEGRAND implemented new KEOR MOD UPS seriesl [T3650]
  • OEM 017: MULTIMATIC UPS model list sorted
  • OEM 017: MULTIMATIC added UPS model series "ML-T" with $$PREXT (Problem T3916 wrong display of load was still present at this time)
  • OEM 017: MULTIMATIC changed SOCOMEC protocol JBUS protocol at "Commlost" detection because of unstable versions found in the field [T3890]
  • OEM 021: EREPI OP 3000 RT changed battery voltage calculation
  • OEM 025: ROTON added Gustav Klein UPS series
  • OEM 032: EFFEKTA added UPS model UDC One 6kVA - UDC One 10kVA
  • OEM 032: EFFEKTA added UPS model series "RT-Industrie"
  • OEM 032: EFFEKTA changed "EFFEKTA OFFICE" series to protocol $$PREPC (after switching to $$APEX)
  • OEM 032: EFFEKTA changed "EFFEKTA OFFICE HOME 800" to protocol $$PREPC
  • OEM 036: ABB protocol $$XONL12C Monitoring Screen wrong data display fixed [T3762]
  • OEM 050: CENTIEL: Fix for modular installations with more than 9 modules [T3919]
  • OEM 051: MITSUBISHI Introduce Mitsubishi's logo and red color in webApp [T3895]
  • OEM 051: Mitsubishi Model 9900D [T3838], Model 9900 AEGIS [T3831], Model 1100B [T3833], Model 1100A [T3832]
  • OEM 051: Mitsubishi Model 9900B [T3834], Model Summit [T3835], Model 9900C [T3836], Mitsubishi Model 9900CX [T3837]
  • OEM 055: COROMATIC changed SOCOMEC protocol JBUS protocol at "Commlost" detection because of unstable versions found in the field [T3890]
  • OEM 058: SIEL added 'Input Auxiliary' status bits to all SIEL_TRAPMSG [T3711]
  • OEM 060: DFM SELECT added SALICRU SLC TWIN PRO2, RT2, SLC CUBE3+, SLC X-PERT, SLC ADAPT X, SLC ADAPT series
  • OEM 062: GUSTAV KLEIN added ROTON UPS Rubin as "Minicompact 2" series
  • OEM 082: SALICRU added ASTRID SCL-80-XPERT B1 series
  • OEM 084: UPS Ltd./ KOHLER Group added PW9250 DPA-250 50kVA and PW9250 DPA-300 50kVA

1.80 - 190618

18. June 2019

Normal Update

Added Features

  • Add ScreenLib Version Info to About Page [T3775]
  • Add SensorLog Chart Start- and Stoptime [T3853]
  • Add BACS Bus Error- and Write-Counters [T3847]
  • Add a user space Out-Of-Memory (OOM) killer [T3801]
  • Add Tooltipps in Menue Sensors > Setup [T3868]
  • Add new user "customer" implemented for access to Logfiles [T3749]
  • Added BACS C41 Module equalizing feature [T3818]

Changed Functionality

  • Improved Email attachment configuration [T3815]
  • Removed snmp recovery feature in favour of [T3801]
  • Full Battery Test runtime now used for autonomy time calculation [T3693]

Bug Fixes

  • Custom Threshold 'Output load' doesn't trigger [T3880]
  • First Modbus request failed, fixed with this version [T3654]
  • Scheduler, Battery Tests fixed email subject and attachment [T3675]
  • UNMS Sitemanager 6 failed to display screen without UPS, fixed with this version [T3854]
  • Email-Traps fixed at logging configuration [T3807]
  • Fixed UPS "Simple Monitor" [T3843]
  • Wrong update information at CS141BSC_LC fixed [T3806]
  • limitation for file size Logo.gif [T3827]
  • Fix for Event-Job Test's at deactivated COM 1 [T3819]
  • Fix for Custom event jobs lost after Fw-Update or Config-Restore [T3813]
  • BACS Email attachment for logs size limit fixed [T3809]
  • Fix for IE 11 download BACSLog [T3808]
  • Fix for BACS Programmer Query function after automatic addressing [T3810]
  • Fix BACS "Enable Max. Voltage Difference" enable/disable [T3794]

OEM customer specific features, changes and fixes

  • OEM 002: New AEG Protect C (LCD) implemented [T3658]
  • OEM 002: AEG modular screen startup time in UNMS improved [T3842]
  • OEM 003: PILLER APOTRANS II fixed display status "0n Bypass"
  • OEM 003: PILLER APOCONV fixed Function Screen [T3855]
  • OEM 003: PILLER APOCONV Text from "UPS" changed to "Converter" [T3856]
  • OEM 003: PILLER AR COMFORT Fulltest cancle function fixed [T3862]
  • OEM 008: LEGRAND new "KEOR MOD" UPS model added [T3650]
  • OEM 004: ONLINE Xanto 1000 (Mod. 2017) fixed SNMP-value for upsOutputSource [T3875]
  • OEM 012: DELTA SNMP card added to CS141 SNMP support [T3846]
  • OEM 012: Added ECUS ups series MRT, ETY, CPA, MRT_X
  • OEM 012: Added Ablerex Mars III $$PRABLER3 added
  • OEM 016: EATON protocol $$MGESHUT - fixes wrong readings at new 9SX series 1000-3000VA [T3839]
  • OEM 017: MULTIMATIC UPS model list sorted
  • OEM 021: ERREPI added RIELLO Transferswitch "Multi Switch ATS"
  • OEM 024: DKC Europe - first implementation of new Modbus Protokoll [T3797]
  • OEM 025: ROTON added "Fianit" series Ablerex $$MBTAURUS, fix for general fault alarm [T3870]
  • OEM 028: AKKUTRONIK Ablerex protocol $$MBTAURUS extended Standard MIB for Ambient Temp [T3824]
  • OEM 028: AKKUTRONIK Continuity Plus protocol $$JBUSDAKER status Overtemperature changed [T3871]
  • OEM 032: Effekta MTX 800KVA -3000KVA added "Battery disconnected" alarm [T3825]
  • OEM 032: Effekta added new UPS Modell Adira T and Adira RT [T3764]
  • OEM 032: Effekta added "RT-Industrie" series
  • OEM 036: ABB protocol $$CONCE - fix for internal event recorder [T3816]
  • OEM 036: ABB protocol $$CONCE - screen startup time in UNMS improved [T3842]
  • OEM 045: WOEHRLE changed names for Nextys DCW20 to UGVNG20
  • OEM 050: CENTIEL protocol $$CENTIEL - fix bad bypass frequency on parallel handling [T3776]
  • OEM 050: CENTIEL preconfigure email-traps for CENTIEL server [T3858]
  • OEM 097: GRUPO PC Mexico implementation TENSE EM-07 in CS141 thru RS485 (and RS232) [T3792]

1.78 - 170318

18. March 2017

Normal Update

Added Features

  • Allow multiple receivers in E-Mail configuration [T3790]
  • UPS communication now configurable either via COM1 RS232 or alternatively via RS485 COM2 [T3686]
  • BACS Scheduler Job added sending logfiles by eMail [T3736]
  • Interval change at scheduled tasks added, interval "yearly" added [T3748]

Changed Functionality

  • BACS delays alarms for Impedance-Out-Of-Upper-Range [T3734]

Bug Fixes

  • UNMS: BACS Status shows "unreachable" with FW 1.76-190214 [T3761]
  • Fix for delay event configuration at Sitemanager 6 for outputs 5-8 [T3531]
  • Updated SNMP library (net-snmp) to version 5.8 [T3653]
  • Fix for BACS display 2 Mio. deg. Fahrenheit at a disscharge [T3777]
  • Regression bugfix since 1.77: Scheduler SMS Job phone number input not possible
  • Regression bugfix since 1.77: Existing scheduler interval configuration lost after update
  • Regression bugfix since 1.77: SNMP "No such Object" for BACS OID's if UPS is disabled [T3786]
  • Regression bugfix for DELTA UPS modular Screen [T3744]
  • DELTA Ultron DPS series temperature N/A fixed [T3756]
  • Webserver hangs if changing the default monitor page [T3787]
  • BACS AC Ripple value must not be used for Discharge Detection [T3783]
  • Email Traps fix - Counterevents now used for cancle alarm conditions [T3747]
  • BACS shows "Error HW Revision/Calibration mismatch" on discharge [T3782]
  • BACS discharge thresholds defaults to a maximum of -15amps [T3727]
  • Port forwarding causes broken links to devices 'monitor' pages [T3332]
  • Disabling "Automatic Logout" generates "Server Error (-1)" [T3697]
  • CON_AUX4 & CON_R_AUX4 configuration bugfix [T3716]
  • Multiple Eventconfiguration / Email Subject bugfix [T3614]
  • At BACKUP the timezone could not be restored [T3739]

OEM customer specific features, changes and fixes

  • OEM 002: New AEG Protect A (LCD) implemented [T3657]
  • OEM 003: PILLER APOCONV AC 100 Screen changes
  • OEM 003: PILLER changed values for datalog for various UPS models
  • OEM 004: XANTO S 1000 shows capacity value with disconnected batteries [T3753]
  • OEM 008: MEGALINE UPS $$ECONT2 Screenbugfixes in the UPS Events History [T3745]
  • OEM 012: Added DELTA "EH" Series $$MDELTA [T3714]
  • OEM 012: Added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 017: Added ABLEREX USV 3rd generation PRABLER3 to Multimatic modellist as ML-xxxxI series
  • OEM 017: Added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 021: ERREPI Added NP10SR-NP30SR series
  • OEM 022: Integration of new UPS Type 15 [T3780]
  • OEM 022: $$EVO: Add SNMP values for upsConfig variables [T3773]
  • OEM 026: CTA added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEm 028: AKKUTRONIK added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 030: UPS SERVIS added "Amberwave AMB3300PRO 10-20k"
  • OEM 032: EFFEKTA FULLTEST changed for MTD 1000XL RT - 3000 XL RT series. At a load change the system will ask - the user to restart the FULLTEST
  • OEM 050: CENTIEL Fixed Bad Input Frequency on the DataLog [T3733]
  • OEM 050: CENTIEL added SNMP MIB objects [T3732]
  • OEM 045: Implementation of Nextys DC UPS via RS485 for Woehrle [T3682]
  • OEM 047: S2S added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 055: COROMATIC Added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 058: SIEL adds 'Input Auxiliary' status bits to all SIEL_TRAPMSG [T3711]
  • OEM 064: LEISTUING Brasil added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 067: COMPUPOWER South Africa added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 077: SNG Australia added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 082: SALICRU changes color scheme from blue to red. First version using red color [T3687]
  • OEM 082: Salicru RM Modbus uses now a not GENEREX standard Modbus mapping
  • OEM 087: ADPOS changes on "Ultron DPS 60-400 kVA" $$MDELTA [T3714]
  • OEM 088: ENERSYS added "Socomec MASTERYS GP4" with JBUSMODULYS
  • OEM 096: BJ BALFOUR China added "Socomec MASTERYS GP4" with JBUSMODULYS