1.76 - 200218

18. February 2020

Important Update

Added Features

  • Check BACS Calibration Bits at startup to detect uncalibrated C 20 modules Rev 3.2 [T3678]: Introducing "Hardware Mismatch/Calibration Bit error" : As soon as FW 1.76 starts, the system compares all Calibration Bits of every module with the reference values of the factory. If a module is found which is not correctly calibrated or has lost for any reason the calibration, the system shows this warning, but will continue to operate. Actions : The enduser should report this error message to our support and ask to replace the module against a calibrate one or get this module recalibrated.
  • SNMP: Add new section upsIdent to the CS1x1 MIB [T3597] and add UPS Bypass-Values to Standard Mapping [T3621]
  • SNMP Trap linked with all new alarms to SNMP "Well Knonw Alarms" whenever a new UPS protocol is implemented [T3607]
  • Sensor Matrix Configuration Implementation [T469/#2797]
  • Add configuration pre-alarms for SM_T_H_COM [T3608]
  • Add more network details to Aboutbox [T3598]
  • User engineer should be able to view the About-Page [T3671]
  • Option to disable Engineer or Guest user [T3568]
  • Offset configuration for Split-Core sensor BACS_CSHXXXX at Sensormanager Screen [T3477]
  • Job Send SMS allows to enter several dial out numbers [T3316]

Changed Functionality

  • Stop BACS equalizing if voltage never converges [T3681]: At older battery systems being retrofitted with BACS it may happen that some batteries do not follow the BACS balancing signal and the voltage deviation does not perform as good as when the batteries were new. In such a case, this new function will watch the Equalizing performance. If the voltage windows does not show any improvement after 4 days (96 hours), the BACS system will trigger a warning and stop disable Equlization automatically if after 4 days (96 hours) without progress and the voltage differences between the batteries per string keeps wider than 0.5 Volt. This feature should make the enduser aware that his batteries have reached their designlife and that it is recommend to swap out those batteries which are not following the trimming signal from BACS.
  • Improved BACS equalizing step response [T3677]: BACS has improved its Equalization functionaliy to improve the efficiency. From this version, BACS will start with 100% Equaliziation on all batteries until these start following the trimming signal and move towards the target voltage. As soon as the batteries start correcting their voltages, the BACS system will lower the equalisation power to improve the energy balance.
  • EventLog System-Eintrag "Information:Battery Health Level Set to xx%" removed [T3635]
  • Remove eMail validation overkill from frontend [T3666]
  • Fetch firmware update notification via HTTPS [T3656]

Bug Fixes

  • SiteMonitor6 acknowledged alarms fixed [T3566]
  • BACS Discharge Counter Automatically Resets after Reboot [T3471]
  • SNMP should display BACS-Module-Temperature in Fahrenheit when selected [T3659]
  • Automatically change the temperature unit on the modbus interface to the unit configured in the UI [T3600]
  • Firefox: Wizard does not start automatically [T3558]
  • Email Option 'CC on scheduled jobs' doesn't send mail [T3484]
  • Fix for delay event configuration at Sitemanager 6 for outputs 5-8 [T3531]
  • Fix for error message "Device not available yet" at a BACS System without configured UPS [T3543]
  • Fix for sporadic 100% equalizing display at all modules [T840/#461]
  • Fix at scheduler for some UPS task are missing for user engineer [T3473]
  • Fix for Datalog Chart [T3586]
  • Fix for Mailserver "TOBIT2" : "AUTH PLAIN" was not correctly handled [T3539]
  • Sporadic BACS_CSH400 current sensor "communication lost" status [T3612] fixed with this version
  • Fix for "Server Error 503" appears at a BACS Bus restart and SNMP Polling is active [T3655]
  • Fix for EventLog, removed internal system informations [T3251]
  • Fix for BACs Programmer page: Impedances were no longer updated when this page has been
    activated/disabled several times [T3544]
  • Fix for CON_R_AUX Output Jobs [T3667]
  • Fix for SNMP query of a full BACS string although one module was lost or displays "n/a" [T3628]
  • Changed SiteMonitor6 Digital Outputs EventLog-Text [T3562] and new default-configuration [T3563]
  • Fix for SiteMonitor6 Outlet-Event-Jobs execution [T3565]
  • Harmonise display format of date & time [T3580]
  • Fix for Scheduled-Job 'Email' to add logfiles to this email [T3602]
  • Fix for User "Engineer" to allow configuration of Jobs on events [T3680]
  • Stratification removal: Equalizing off/on via Scheduler [T1355/#789] added
  • SMTCOM / SMTHCOM showed at FW 1.74 in the UNMS the value "10", fixed with this firmware
    and latest UNMS update
  • Fix for Logfile submenue at hardware platform CS141BL [T3746]

OEM customer specific features, changes and fixes

  • OEM 002: New AEG Protect A (LCD) implemented [T3657]
  • OEM 002: AEG version of protocol $$ZINTOE Output OFF Status corrected [T3634]
  • OEM 002: AEG change on Protect 2.33 2.0 $$MBCUBE2 SNMP_CUBE [T3249]
  • OEM 003: PILLER APOTRANS II error message "Failure Source B" at normal ooperation [T3527]
  • OEM 004: ONLINE $$XONL12C added 3 UPS logfiles [T3540]
  • OEM 004: ONLINE $$XONL12C, "UPS Status = Diagnostic Test Failed" after Battery Test fixed [T3466]
  • OEM 006: VERTIV/EMERSON: New UPS modellist with IS-UNITY-DP
  • OEM 007: First version of EUROTECH, taking over RIELLO firmware
  • OEM 007: EUROTECH $$GPSER wrong outputpower unit fixed [T3617]
  • OEM 008: LEGRAND Megaline, $$ECONT2, Output Power display fixed [T3577]
  • OEM 008: LEGRAND Keor T, $$PYRDSP, wrong input high status fixed [T3629]
  • OEM 008: LEGRAND $$JBUSDAKER Outputpower changed [T3584]
  • OEM 008: LEGRAND $$TRIMODHE ("TRIMOD HE") display problems with Microsoft Edge at "current alarms" [T3581]
  • OEM 008: LEGRAND Trimod, $$TRIMOD, Event Job "Switch Phase On/Off", Parameters added [T3576]
  • OEM 008: LEGRAND $$JBUSDAKER: Smaller Protocoll changes [T3006]
  • OEM 008: LEGRAND Keor SP, $$KEORSP, Screen changed [T3649]
  • OEM 012: Mitsubishi 1100A/B, $$SALISEC, Bypass Frequency Wert SNMP fixed [T3647]
  • OEM 012: Mitsubishi Missing Input Values for 1100A/B [T3583]
  • OEM 012: Mitsubishi implemented 1100A_B Protocol [T3601]
  • OEM 012: KSTAR 2 Modbusprotocol implementation [T3467]. Also added to OEMs 11,30,32,41,57,58,61,65,67,87,97 and 99
  • OEM 012: VOLTRONIC Taurus Pro, M4T Evolution $$MBCUBE2, Added extra SNMP values [T3249]
  • OEM 017: Multimatic added GROUP MTS Transferswitch from RIELLO
  • OEM 019: BENNING UPS ENERTRONIC I 3-3 synchronize Date & time fixed [T3624]
  • OEM 019: BENNING added S3100, S3300 series
  • OEM 021: $$BNTUSB Calculation Batteriecapacity fixed [T3537]
  • OEM 028: AKKUTRONIK ABLEREX $$MBTAURUS changed Device Temperature and Ambient Temperature [T3626]
  • OEM 028: AKKUTRONIK added X-Plus TE 80 Kva, MOD HP2, MPM10-20
  • OEM 032: EFFEKTA $$XONL12D Full Battery Test fixed [T3618]
  • OEM 036: ABB DPA, $$CONCE, 3 Modules wrong data fixed (173V, 174V, 175V Inputvoltage) [T3575]
  • OEM 041: INFORM/LEGRAND: Pyramid DSP 10K, $$PRPYRDSP, UPS Screen fixed [T3482]
  • OEM 042: First version of THYCON Australia, taking over SINETICA/UNITE UK
  • OEM 058: SIEL $$SIELEMM: Add 'Input Auxiliary' to SIEL_TRAPMSG [T3513]
  • OEM 058: SIEL $$MEGAE: Add the 'SIEL_TRAPMSG' feature [T3377]
  • OEM 058: SIEL TRAPMSG: 'History Full', 'UPS connection lost/restored', AUX-Ports ergänzen [T3569]
  • OEM 064: First version for LEISTUNG Brazil, taking over BENNING MCU
  • OEM 070: ASTRID wrong output power via SNMP for $$EVO5 fixed [T3609]
  • OEM 074: CERTA UPS: Certa C800 $$MBSALIRM, UPS Status Battery Bad, Depleted Battery, Output Off fixed [T3446]
  • OEM 078: SICOTEC add GROUPS MTS and GROUPSYS series
  • OEM 077: SNG Power Australia: $$MBCUBE2, Added extra SNMP values [T3249]
  • OEM 078: SICOTEC: $$MBCUBE2, Added extra SNMP values [T3249]
  • OEM 078: SICOTEC added STS Riello
  • OEM 082: SALICRU $$CYBEN ("SPS ADV R"): Displayed wrong Status "UPS Output Off" [T3631]
  • OEM 082: SALICRU "--SLC CUBE 3 series 2012--", $$MBCUBE2, Added extra SNMP values [T3249]
  • OME 084: UPS LTD changed the name to KOHLER UPS Ltd.
  • OEM 087: ADPOS DELTA "Ultron DPS 60-400 kVA", $$MDELTA, Änderungswünsche [T3714]
  • OEM 099: AGIT Poland fixed $$XONL12C for Agpower C RT 1-10kVA, Out-freq. and switching outlets [T3698]
  • All OEM: Modellname APC Smart UPS / Smart UPS has been changed to "APC Smart/AP9620 Legacy Card" or "Smart UPS/AP9620 Legacy Card"

1.74 - 181025

25. October 2018

Important Update

Added Features

  • First version for SITEMONITOR 6 [T99 / #3273][T3564][T3469]
  • New configuration restore option without network settings [T3271]
  • Verify IP Gateway in subnet [T3331]
  • 2nd DNS server configuration [T570/#2666]
  • New CSHxxx Split-Core current sensors show AC ripple current [T3319]
  • Additional Modbus Registers for BACS [T3468]
  • Cancel RCCMD Shutdown Button introduced [T3502]
  • BACS added stringvoltage via Modbus [T3542]

Changed Functionality

  • BACS VIEWER requires with this firmware at least windows W2012R2

Bug Fixes

  • Unplugging power cord <10sec. after network configuration corrupts webserver. Fixed with this version [T3592]
  • Minor Spelling errors on CS141 [T3445]
  • MIB-Walk at BACS-Modulen shows 512 entries, although only a few modules were installed. [T3475]
  • At JOB configuration for "UPS Outlets" removed Port numbers [T3546]
  • Fixes for EVENT configuration [T3495]
  • SENSORMANAGER, SITEMANAGER, SITEMONITOR show now all Alarm thresholds [T3557]
  • Fix at BACS Programmer Webinterface to reset the IDs correct [T3501]
  • BACS Programmer activation button changed [T3500]
  • UPS Time Synchronization Logentry removed [T3518]
  • Hostnamens allows now special characters [T3029]
  • UPS Event configuration now possible although UPS communication is interrupted [T3510]

OEM customer specific features, changes and fixes

  • OEM 003: PILLER $$PILMOD10: At configuration Recharge-Time=0 UPS communication blocked, fixed with this version [T3508]
  • OEM 003: PILLER AR Comfort pos. and neg. battery string added
  • OEM 004: ONLINE UPS changed temperature range of XANTO S 100003/1 2017 from 50°C to 55°C
  • OEM 007: EUROTECH and all other customers using RIELLO GPSER: Added Datalog pos. and neg. Batteryvoltage [T3503]
  • OEM 008: LEGRAND: Implemented Keor SP [T3458] (only UPSMAN software, not yet available in CS141 because of missing USB support
  • OEM 012: GENEREX: Added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 012: GENEREX: Added various G-TEC UPS models SR (GPSER RIELLO) LB/AR (SENTRY/RIELLO), TP, ZP, ZS, AP, MUST (CENTRALION),
  • ZY (CYBERPOWER)
  • OEM 026: CTA added CENTIEL UPS
  • OEM 030: UPS SERVIS added AMBERWAVE series
  • OEM 032: EFFEKTA changed Thor Modbus/Triton 10-500 kVA ext.port, $$KSTAR UPS screen [T3485]
  • OEM 032: EFFEKTA series MTX (VOLTRONIC) added
  • OEM 032: EFFEKTA Thor Modbus/Triton 10-500 kVA ext.port, $$KSTAR, Batteryvoltage now 3phase log [T3429]
  • OEM 036: ABB CONCE protocol added Bypass Voltage + Frequency via SNMP and MODBUS [T3505]
  • OEM 036: ABB (and all other ABB customers using modular ABB products)shows at startup phase the UPS modules found at
  • CS141/BACS so that the enduser can see that the device is still busy [T453 #2821]
  • OEM 048: THRIATLON UPS 'Master Dialog RT 30' was added to model list [T3474]
  • OEM 050: CENTIEL: Fix for wrong 'Input Frequency' display/value for 50Hz module [T3591]
  • OEM 054: AMG added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 062: GUSTAV KLEIN Screenchange USV-4608EK, $$KLEIN1 [T3526]
  • OEM 065: PTI added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 067: COMPUPOWER added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 069: SBS added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 074: CERTAUPS removed all UPS device except CERTA 800 series
  • OEM 079: ELTEK added Modulon NH Plus-Series
  • OEM 082: SALICRU extended MODBUS Section for SLC ADAPT and SLC ADAPT X [T3451]
  • OEM 097: POWERALL MEXICO Adding P+01K-Y KSTAR UPS Models to OEM ID 97 [T3488, T3445]
  • OEM 098: GENESYS added new model "Mitsubishi/Toshiba 9xx SEC 9600b+" [T3448]
  • OEM 099: AGIT POLAND Additional dispaly for Output Power in KW Screen $$MBSALIRM2 [T3481]

1.72 - 180616

16. June 2018

Normal Update

Added Features

  • BACS Feature against stratification - Equalizing/Balancing can now be activated/deactivated via Scheduler [T1355/#789]

Changed Functionality

  • Option 'Synchronize with UPS Device' moved to page System → Date & Time
  • Redesign of BACS Programmer, improved user interface and acoustical feedback during programming operations
  • BACS option 'Optimize Scan' is now off by default
  • Decreased BACS thermal-runaway temperature lower limit to 2.0
  • Removed irrelevant logentry "DeviceIOControl" [T3434]
  • Improved Certifacte upload to avoid that webserver stucks [T3443]

Bug Fixes

  • Display SENSORMAN2 fixed, removed invalid 4 inputs and outputs in the webinterface
  • Fixed event section at SITEMANAGER 6 [T3463]
  • Fix for MS Internet Explorer login via https [T3310]
  • Fix for wrong BACS Modul Temperature at Fahrenheit via Modbus [T3452]
  • Fix for bulk edit operations of EventJobs which did exceed max. webserver request size [T3161]
  • Fix for manual setting timezone [T3390]
  • Fix for UPS Event Communication Lost not recognized wird via MODBUS Adresse 134 nicht erkannt [T3431]
  • Deactivation of Webserver now possible [T3461]
  • Fix for CON_R_AUX configuration to avoid messages "Pending Operation" [T3410] and "Server Error (420)" [T3335]

OEM customer specific features, changes and fixes

  • OEM 002: AEG Rollback T3393: In UPS-Functions die 'UPS Control' Funktionalität wieder einfügen [T3449]
  • OEM 002: AEG UPS-Screens with 'UPS Events' removed the Event-Category [T3433]
  • OEM 003: PILLER changed modells "APOJET R II", "APOJET T II", "APOJET LVR" and "MGE-SET"
  • OEM 003: PILLER Test #0131 Umschaltung der Seiten im Chrome Browser [T3427]
  • OEM 003: PILLER Test #0130 APOJET R II - Funktionen [T3426]
  • OEM 003: PILLER Test #0129 DataLog Messwerte APOJET R II [T3425]
  • OEM 003: PILLER Test #0127 APOJET R II – Statustexte über dem Blindschaltbild [T3423]
  • OEM 003: PILLER Test #0126 APOJET R II Seite OUTPUT2 Einblenden/Ausblenden [T3422]
  • OEM 003: PILLER Test #0125 APOJET R II Seite OUTPUT, OUTPUT1, BOX Text [T3421]
  • OEM 003: PILLER Test #0124 APOJET R II Seite OUTPUT DC [T3420]
  • OEM 003: PILLER Test #0123 APOJET R II Seite GENERATOR Text [T3419]
  • OEM 003: PILLER Test #0122 APOJET R II Displayfoliendarstellung [T3418]
  • OEM 003: PILLER Test #0121 APOTRANS III Phasenwinkelanzeige [T3417]
  • OEM 003: PILLER Test #0120 DataLog Messwerte UNIBLOCK UBT IV [T3416]
  • OEM 003: PILLER Test #0118 APOSTAR AS IV, Status Bar LED und Texte [T3414]
  • OEM 003: PILLER Test #0115 Status des SNMP Adapters, Modbus Adressen 3002..3076 [T3373]
  • OEM 030: UPS SERVIS Latvia has added C300R series
  • OEM 032: Effekta Office Series changed from protocol APEX to new PREPC protocol
  • OEM 045: WHOERLE added "WISUS WP-T" from CENTIEL
  • OEM 050: CENTIEL Status-Button showed discharged batteries, fixed with this version [T3462]