1.88 - 200218

18. February 2020

Normal Update

Added Features

  • Added BACnet/IP Slave Implementation [T690/#2409]
  • Added remote Syslog option to send EventLog messages to a remote syslog server [T4000]
  • Adding Output Energy Consumption (kWh) for some UPS [T4044]
  • Datalog Chart selection now storable [T3882]
  • SNMP CLI-Tools multi-OID requests for table values added [T3995]

Changed Functionality

  • BACS com-lost timeout for modules and sensors decreased
  • SNMP deactivating the UPS/BACS agent stops also SNMP OS service [T4030]
  • Removed : GSM IP Modem configuration

Bug Fixes

  • Bugfix memory leak in UPS model “SNMP UPS-RFC 1628 compliant” [T3111]
  • Bugfix for SNMP V3: Large GetBulk queries can crash the service [T4029]
  • Regression bugfix Email Job: Option "Attach UPS Alert History" was missing [T3815]
  • Bugfix for Internet Explore IE 11 - click on "About" did freeze the browser [T3946]
  • Bugfix for BACS Current sensor - displayed last measured value after comm. lost, now shows "n/a" [T3829]
  • Warning at UPS custom threshold configuration if this gets lost after firmware update [T4048]
  • Minor Bugfix for WOL: Job configuration placeholder is misleading [T4007]
  • Minor Bugfix for Setup Wizard: Tooltips are 'hidden' when autostart after Fw-Update with "Reset to factory" [T3972]

OEM customer specific features, changes and fixes

  • OEM 008: LEGRAND Keor T, $$PRPYRDSP: Make available more values via Modbus and SNMP [T4015]
  • OEM 036: ABB removed Custom Test from Device Function Page [T4040]
  • OEM 050: $$CENTIEL: Retrieving UPS Events History fails if UPS has no events [T4065]
  • OEM 051: MITSUBISHI requires a password change before first usage [T3830]
  • OEM 055: COROMATIC fix for Netys PR RT 1700-3300VA ($$JBUSP) at UPS Functions, "Restore with Duration" [T4035]

1.86 - 191203

3. December 2019

Security Update

Added Features

  • Added support for 4G SMS modem [T3981]
  • Added SNMP and Modbus stati for GX_R_AUX [T3860]
  • Added configurable BACS Resistance measurement Interval and Time [T3913]
  • Added SiteManager/Monitor GSM-Modem configuration [T3411]
  • Added Sitemonitor 6 Outputs with EVENT configuration [T3817]
  • EventLog time now showing seconds [T3976]

Changed Functionality

  • Securing password encryption in configuration files [T565/#2673]
  • Securing Cross-site scripting (XSS) vulnerability in "jQuery UI" [T3991]

Bug Fixes

  • Regression bugfix for email without authentication [T565 + T4026]
  • Regression bugfix for FW 1.82 :RCCMD transmission of SSL encrypted messagges [T3999]
  • SITEMANAGER 6 SM2-T-DIG Temperature fix [T3974]
  • Internet Explorer requires some config pages to refresh to show changes [T4003]
  • Bugfix for BACS C41 Module configuration [T3984]
  • Bugfix for Download BACSLog [T3977]
  • Bugfix for CS141 Threshold Alarms display in the UNMS [T3346]
  • Email-Traps SM_T_H_COM Thresholds and Channel names fixed [T3960]
  • Regression bugfix for FW 1.80 : An EventJob with a start delay does delay also other jobs of the same event [T3982]
  • Bugfix for Microsoft Internet Explore 11: About Page causes webpage to stop working. Any other browser works fine.

OEM customer specific features, changes and fixes

  • OEM 002: AEG added $$MBSALIRM2 as "AEG Protect Flex" [T3954]
  • OEM 008: LEGRAND added Daker DK Plus $$JBUSDAKER with smaller changes [T3935]
  • OEM 025: ROTON changed their logo
  • OEM 028: AKKUTRONIK added WOEHRLE/CENTIEL WISUS UPS to their portfolio
  • OEM 036: ABB added "BATTERY CURRENT/UPS Seconds on Battery" in UPS Screen [T3914]
  • OEM 045: WOEHRLE added Modbus and SNMP wellknown alarm traps for "UGVNG 20" &d "DC USV Nextys" Transferswitches STS Tumel [T3238]
  • OEM 050: CENTIEL added for $$CENTIEL new Events [T3979] and changed calculation of UPS power
  • OEM 050: CENTIEL changed boot up phase to avoid invalid Modbus Values during system boot [T3343]
  • OEM 090: KESS added "Kess UPS-52RT" with $$PREXTZINTO and using UPS Standard screen [T3963]
  • OEM 090: KESS "Kess UPS-92RT" with $$PREXT changed the display für Outputvalues [T3962]

1.84 - 191001

1. October 2019

Normal Update

Changed Functionality

  • BACS increased max. log folder size to 30 MB (before 20MB) and max. file size to 5 MB (before 2 MB)
  • BACS C40 condensator 9V changed to 16V to reduce internal heat emissions, visible in BACS VIEWER

Bug Fixes

  • SyncTime Job produces misleading log message [T3949]
  • Battery Current values in BACS VIEWER factor 10 too high, fixed with this version
  • Logfile rotation regression bugfix from 1.82 fixed with this version
  • Regression bug in 1.82 removed Email BCC, now back again

OEM customer specific features, changes and fixes

  • OEM 002: AEG added Protect Plus S300
  • OEM 002: AEG read internal error recorder fixed for Protect D [T50]
  • OEM 002: AEG Protocol MBSALIRM2 added Modbus by AUX and SENSORMAN Addresses [T3930]
  • OEM 003: PILLER APOJET S II – Geräte -> Umformer -> Funktionen, Texte (Test #0147) [T3704]
  • OEM 003: PILLER APOCONV –> Geräte -> Umformer -> Funktionen (Test #0146) [T3703]
  • OEM 003: PILLER APOCONV – Text in Out1 Seite (Test #0145) [T3702]
  • OEM 003: PILLER APOCONV – deutsche Texte (Test #0144) [T3701]
  • OEM 003: PILLER APOCONV – Page Default (Test #0143) [T3700]
  • OEM 003: PILLER APOTRANS II / APOTRANS II<125A - inverses Blinken LEDs (Test #139) [T3641]
  • OEM 003: PILLER APOTRANS II / APOTRANS II<125A - Seite Neutralleiterströme abgeschnittener Text-Deutsch (Test #0137) [T3640]
  • OEM 003: PILLER APOTRANS II /APOTRANS II<125A - Netztransferzähler Übersetzung-Deutsch (Test #0136) [T3639]
  • OEM 003: PILLER APOTRANS II / APOTRANS II<125A - Seite Neutralleiterströme Übersetzung/Überlappung-Deutsch (Test #0135) [T3638]
  • OEM 003: PILLER APOTRANS II / APOTRANS II<125A - Displayseite Betriebsstunden Übersetzung-Deutsch (Test #0134) [T3637]
  • OEM 007: EUROTECH removed the RIELLO Logo and replaced it by EUROTECH logo
  • OEM 008: LEGRAND Daker DK Plus, $$JBUSDAKER minor changes [T3935] and [T3881]
  • OEM 008: LEGRAND DK Plus series added new SNMP section SNMP_JBUSGEN with more values
  • OEM 008: LEGRAND Sorting UPS modellist new arranged
  • OEM 008: LEGRAND Protocol $$PYRDSP always read output as 3-phases values
  • OEM 012: Added KSTAR series MEMOPOWER 1-Phase
  • OEM 013: KESS added "E-Series DX"
  • OEM 017: MULTIMATIC changed ML-x000I V2 series from protocol PRABLER3 to JBUSDAKER
  • OEM 017: MULTIMATIC ML-xxxxI V2 addded new SNMP section SNMP_JBUSGEN with more values
  • OEM 020: DRS PIVOTAL POWER USA $$SALISEC MIB OID upsOutputSource not displaying the correct value when On Bypass [T3826]
  • OEM 025: ROTON Rubin Plus 1-3 KVA addded new SNMP section SNMP_JBUSGEN with more values
  • OEM 028: AKKUTRONIK Continuity Plus addded new SNMP section SNMP_JBUSGEN with more values
  • OEM 030: UPS SERVICE Amberwave AMB RT/T 1-3 kVA added new SNMP section SNMP_JBUSGEN with more values
  • OEM 032: EFFEKTA "EFFEKTA MTX 800" ($$PREXT): USV-Screen zeigt falsche Lastwerte [T3916]
  • OEM 041: INFORM Protocol $$PYRDSP always read output as 3-phases values
  • OEM 045: WOERHLE added Transferswitch STS Tescom and did corrections on Signalerror [T3238]
  • OEM 045: WOEHRLE CONVERT II added new SNMP section SNMP_JBUSGEN with more values
  • OEM 047: S2S DK Plus xxxx added new SNMP section SNMP_JBUSGEN with more values
  • OEM 050: CENTIEL UPS Events (History) - order of events changed [T3828]
  • OEM 050: CENTIEL New default for EMAILTRAPS
  • OEM 058: SIEL Savepower-EVO: Script-error fixed and missing UPS values added [T3901]
  • OEM 059: ALPHA Continuity Plus added new SNMP section SNMP_JBUSGEN with more values
  • OEM 062: GUSTAV KLEIN Minicompact 2 added new SNMP section SNMP_JBUSGEN with more values
  • OEM 078: SICOTEC SPS ADV RT2 added new SNMP section SNMP_JBUSGEN with more values
  • OEM 082: SALICRU SPS ADV RT2 added new SNMP section SNMP_JBUSGEN with more values
  • OEM 090: KESS added UPS-52RT series (VOLTRONIC PREXTZINTO)
  • OEM 090: KESS added UPS-92RT series (VOLTRONIC PREXT)